Low NOx 3-pass flue and smoke tube steam boiler
KDF series
Main specifications
Full specification table| Model | KDF-1000 ~ KDF-10000 · 13 models |
|---|---|
| Rated evaporation | 1,000 – 10,000 kg/h |
| Maximum operating pressure | 1{10} Mpa[kg/㎠] |
| Efficiency | 88% |
| Power | 380V / 440V x 3ø x 60Hz |
Feature
-
3-pass structure
-
Easy to replace and repair the flue with handy open-close 2-door smoke room design.
-
The boiler has excellent sudden load fluctuation response ability as the body contains large amount of retained water.
-
High heat absorption rate by designing the rear combustion chamber wet type
-
The flue tube can be used safely as it is designed to cope with thermal expansion by making it in a waveform.
Standard specifications
KDF seriesStandard specifications for 3-pass flue and smoke tube type of low NOx boiler KDF series
| Category | Unit | KDF -1000 | KDF -1500 | KDF -2000 | KDF -2500 | KDF -3000 | KDF -3500 | KDF -4000 | KDF -4500 | KDF -5000 | KDF -6000 | KDF -7000 | KDF -8000 | KDF -10000 | |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Boiler specifications | Rated evaporation | kg/h | 1,000 | 1,500 | 2,000 | 2,500 | 3,000 | 3,500 | 4,000 | 4,500 | 5,000 | 6,000 | 7,000 | 8,000 | 10,000 |
| Medium hot water | Gcal/h | 1G | 1.5G | 2G | 2.5G | 3G | 3.5G | 4G | 4.5G | 5G | 6G | ||||
| Maximum operating pressure | Mpa[kg/㎠] | 1{10} | |||||||||||||
| Heat output | MW | 0.75 | 1.12 | 1.50 | 1.87 | 2.25 | 2.62 | 2.99 | 3.37 | 3.74 | 4.49 | 5.24 | 5.99 | 7.48 | |
| kcal/h | 643,700 | 965,550 | 1,287,400 | 1,609,250 | 1,931,100 | 2,252,950 | 2,574,800 | 2,896,650 | 3,218,500 | 3,862,200 | 4,505,900 | 5,149,600 | 6,437,000 | ||
| Efficiency | % | 88% | |||||||||||||
| Heating area | ㎡ | 26 | 33 | 41 | 51 | 62 | 70 | 81 | 91 | 101 | 110 | 121 | 138 | 175 | |
| Power | V | 380V / 440V x 3ø x 60Hz | |||||||||||||
| Burner | Combustion control | - | HI - LOW - OFF / HI - MID - LOW - OFF / proportional control | ||||||||||||
| Burner type | Forced mixing type | ||||||||||||||
| Ignition method | Pilot ignition method | ||||||||||||||
| Fuel consumption | LNG | N㎥/h | 73.1 | 109.7 | 146.3 | 182.9 | 219.4 | 256.0 | 292.6 | 329.2 | 365.7 | 438.9 | 512.0 | 585.2 | 731.5 |
| LPG +AIR | 52.2 | 78.4 | 104.5 | 130.6 | 156.7 | 182.9 | 209.0 | 235.1 | 261.2 | 313.5 | 365.7 | 418.0 | 522.5 | ||
| Propane | 32.7 | 49.0 | 65.3 | 81.6 | 98.0 | 114.3 | 130.6 | 146.9 | 163.3 | 195.9 | 228.6 | 261.2 | 326.6 | ||
| Butane | 24.8 | 37.2 | 49.6 | 62.0 | 74.4 | 86.8 | 99.2 | 111.6 | 124.0 | 148.8 | 173.6 | 198.4 | 248.0 | ||
| Power consumption | Water pump | Model | Vertical multi-step | ||||||||||||
| kW x Quantity | 2.2 X 2 | 3.0X2 | 3.7X2 | 5.5X2 | 7.5X2 | ||||||||||
| Blower | kW | 3.7 | 7.5 | 11 | 15 | 19 | 22 | ||||||||
| Connection diameter | Steam outlet | A | 50 | 65 | 80 | 80 | 100 | 100 | 100 | 100 | 125 | 125 | 150 | 150 | 200 |
| Water inlet | 25 | 25 | 25 | 25 | 40 | 40 | 40 | 40 | 40 | 40 | 40 | 40 | 50 | ||
| Drainage outlet | 40 | 40 | 40 | 40 | 40 | 40 | 40 | 40 | 40 | 50 | 50 | 50 | 50 | ||
| Gas inlet | 25 | 40 | 40 | 40 | 40 | 40 | 50 | 50 | 50 | 65 | 65 | 80 | 80 | ||
| Safety valve | 25 X 1 | 32X1 | 40X1 | 32X1/25X1 | 40X1 / 25X1 | 40X2 | 40x1/32X1 | 40X2 | 50 X 1 / 40 X 1 | 65X1 / 50X1 | |||||
| Exhaust outlet | mm | 250X400 | 250X550 | 300X600 | 300X750 | 400X750 | 400X800 | 400X950 | 500X950 | 500X950 | 600X950 | 600X900 | 700X950 | 700X950 | |
| Flue | ø | 300 | 350 | 400 | 450 | 500 | 550 | 600 | 600 | 650 | 650 | 650 | 700 | 800 | |
| External size | Width(W) | mm | 2,178 | 2,278 | 2,408 | 2,408 | 2,498 | 2,605 | 2,705 | 2,852 | 2,852 | 2,660 | 2,810 | 3,010 | 3,120 |
| Length(L) | 3,553 | 3,715 | 3,968 | 4,448 | 5,069 | 5,075 | 5,275 | 5,375 | 5,575 | 5,600 | 6,200 | 6,500 | 6,960 | ||
| Height(H) | 2,796 | 2,896 | 3,031 | 3,031 | 3,131 | 3,251 | 3,351 | 3,501 | 3,501 | 2,860 | 3,060 | 3,250 | 3,320 | ||
| Weight | Ton | 4.6 | 6.8 | 8.4 | 9.1 | 11.0 | 12.6 | 13.5 | 15.4 | 15.9 | 16.4 | 17.6 | 19.2 | 22.5 | |
The above specification table is indicated as follows. Fuel consumption is based on the low-level calorific value.
- LNG : 10,000 kcal/N㎥
- LPG + AIR : 14,000 kcal/N㎥
- Propane(LPG) : 22,400 kcal/N㎥
- Butane : 29,500 kcal/N㎥
The rated evaporation amount is based on the water supply temperature of 20℃ and steam pressure of 1MPa.
These specifications are subject to change without prior notice to improve product performance.
Consultation and quotes
Tell us where the boiler will be installed and what it is for.
Our engineers will get back to you.