High efficiency low NOx Condensing boiler

KDFC series

Main specifications

Full specification table
ModelKDFC-1000HEX ~ KDFC-100HEX · 13 models
Rated evaporation1,000 – 10,000 kg/h
Maximum operating pressure1{10} Mpa[kg/㎠]
Efficiency99%
Power380V / 440V x 3ø x 60Hz

Feature

  • The boiler maximizes energy efficiency by recovering the sensible heat contained in the exhaust gas and the latent heat of water vapor.

  • The boiler is integrated with auxiliary facilities such as the blower, water pump, panel water meter and automatic blow device.

  • The boiler does not require a separate installation space by attaching the original air pre-heater and economizer directly to the boiler.

Standard specifications

KDFC series

Standard specifications for condensing flue and smoke tube type of steam boiler KDFC series

Item Model Unit KDFC -1000HEX KDFC -15HEX KDFC -20HEX KDFC -25HEX KDFC -30HEX KDFC -35HEXB KDFC -40HEXB KDFC -45HEX KDFC -50HEXB KDFC -60HEX KDFC -70HEX KDFC -80HEX KDFC -100HEX
Boiler specifications Rated evaporation kg/h 1,000 1,500 2,000 2,500 3,000 3,500 4,000 4,500 5,000 6,000 7,000 8,000 10,000
Medium hot water Gcal/h 1G 1.5G 2G 2.5G 3G 3.5G 4G 4.5G 5G 6G
Maximum operating pressure Mpa[kg/㎠] 1{10}
Heat output MW 0.75 1.12 1.50 1.87 2.25 2.62 2.99 3.37 3.74 4.49 5.24 5.99 7.48
kcal/h 643,700 965,550 1,287,400 1,609,250 1,931,100 2,252,950 2,574,800 2,896,650 3,218,500 3,862,200 4,505,900 5,149,600 6,437,000
Efficiency % 99%
Heating area ㎡ 16 26 34 40 47 54 61 68 74 91 104 119 150
Power V 380V / 440V x 3ø x 60Hz
Burner Combustion control - HI - LOW - OFF / HI - MID - LOW - OFF / proportional control
Burner type Forced mixing type
Ignition method Pilot ignition method
Air pre-heater Model - Heat pipe type
Product weight kg 194 219 255 278 320 362 371 388 403 529 613 678 749
Water pre-heater Model - Spiral type
Product weight kg 164 279 330 376 388 473 512 544 631 674 687 726 894
Fuel consumption LNG N㎥/h 65.0 97.5 130.0 162.6 195.1 227.6 260.1 292.6 325.1 390.1 455.1 520.2 650.2
Propane N㎥/h 29.0 43.5 58.1 72.6 87.1 101.6 116.1 130.6 145.1 174.2 203.2 232.2 290.3
kg/h 57.0 85.5 114.0 142.6 171.1 199.6 228.1 256.6 285.1 342.2 399.2 456.2 570.3
Power consumption Water pump Model Vertical multi-step
kW x Quantity 2.2 X 2 3.0X2 3.7X2 5.5X2 7.5X2
Blower kW 3.7 7.5 11 15 19 22 30 37
Connection diameter Steam outlet A 50 65 80 80 80 80 100 100 125 125 150 150 200
Water inlet 25 25 25 25 40 40 40 40 40 40 40 40 50
Drainage outlet 40 40 40 40 40 40 40 40 40 40 40 50 50
Gas inlet 25 40 40 40 40 40 50 50 50 50 50 65 65
Safety valve 25 X 1 40 X 1 40 X 1 / 25 X 1 40x2 50 X 1 / 40 X 1 65X1 / 50X1
Exhaust outlet mm 300x430 380x475 400x600 400x600 380x700 480x700 480x720 480x720 480x770 546x750 546x860 546x930 600x950
Flue ø 300 350 400 400 450 450 500 550 550 600 650 700 800
External size Width(W) mm 1,826 2,111 2,136 2,241 2,351 2,416 2,461 2,461 2,531 2,596 2,828 2,871 3,140
Length(L) 3,566 3,599 3,828 3,938 4,142 4,865 4,657 5,057 4,953 5,455 5,645 5,992 6,873
Height(H) 2,781 3,061 3,236 3,326 3,376 3,324 3,394 3,394 3,660 3,862 3,945 4,157 4,328
Weight Ton 4.0 5.3 6.1 6.9 7.7 8.8 9.5 10.0 11.2 13.0 14.5 17.0 20.5

The above specification table is indicated as follows. Fuel consumption is based on the low-level calorific value.
- LNG : 10,000 kcal/N㎥
- Propane(LPG) : 22,400 kcal/N㎥
The rated evaporation amount is based on the water supply temperature of 20℃ and steam pressure of 1MPa.
These specifications are subject to change without prior notice to improve product performance.

Consultation and quotes

Tell us where the boiler will be installed and what it is for.