Two circuit flue and smoke tube hot water boiler
SUPER series
It is a high-performance, high efficiency boiler that has unique 3-pass combustion structure and eccentric corrugated combustion chamber that facilitates hot water circulation inside the boiler body and greatly increases the heat exchanger heat absorption.
Main specifications
Full specification table| Model | SUPER-30 ~ SUPER-100 · 6 models |
|---|---|
| Rated heat output | 0.35 – 1.16 MW (300,000 – 1,000,000 kcal/h) |
| Efficiency | 88% |
Feature
-
Both hot water and heating can be solved at the same time with one boiler.
-
Scale generation and dissolved oxygen corrosion are reduced by attaching the heat exchanger to the inside of the boiler.
-
Smoking chamber has no risk of collapse as it is made with fire-resistant bricks and is made as water-room type to maximize heating surface.
-
The heating surface of the heat exchanger, which is the life of a hot water boiler, is expanded as much as possibly by designing the copper pipe installation of the heat exchanger with the largest capacity in Korea (Containing 8-10% more than the actual required amount).
Standard specifications
SUPER seriesStandard specifications for the flue and smoke tube type of hot water boiler
| Category | Unit | Standard specifications for flue and smoke tube 2-circuit type of SUPER series | ||||||
|---|---|---|---|---|---|---|---|---|
| SUPER - 30 | SUPER - 40 | SUPER - 50 | SUPER - 60 | SUPER - 80 | SUPER - 100 | |||
| Boiler body | Rated heat output | MW | 0.35 | 0.47 | 0.58 | 0.7 | 0.93 | 1.16 |
| kcal/h | 300,000 | 400,000 | 500,000 | 600,000 | 800,000 | 1,000,000 | ||
| Maximum operating pressure | Mpa[㎏/㎠] | 0.35 [3.5] | 0.35 [3.5], 0.7 [7], 1.0 [10] (Optional) | |||||
| Efficiency | % | 88% | ||||||
| Operating power | V | 220V x 3ø x 60Hz / 380V x 3ø x 60Hz x 4W | ||||||
| Burner output | kW | 0.3(0.25) | 0.3(0.35) | 0.47(0.47) | 2.2 | 2.2 | 0.7 | |
| Fuel consumption | Boiler kerosene | kg/h | 39.8 | 53 | 66.3 | 79.5 | 106 | 132.5 |
| Heavy oil | 36.7 | 49.1 | 61.3 | 73.6 | 98.1 | 122.6 | ||
| LNG | N㎥/h | 34.1 | 45.4 | 56.8 | 68.2 | 90.9 | 113.6 | |
| Propane | 15.2 | 20.3 | 25.4 | 30.4 | 40.6 | 50.7 | ||
| LPG+AIR | 24.7 | 32.9 | 41.1 | 49.4 | 65.8 | 82.3 | ||
| Connection diameter | Heating Inlet and Outlet | A | 80 | 100 | 100 | 125 | 125 | 150 |
| Heating Inlet and Outlet | 50 | 50 | 50 | 50 | 65 | 65 | ||
| Drainage valve | 32 | 32 | 32 | 40 | 50 | 50 | ||
| Flue | ø | 250 | 300 | 300 | 300 | 350 | 400 | |
| External size | Width(W) | mm | 1,440 | 1,500 | 1,500 | 1,500 | 1,680 | 1,720 |
| Length(L) | 2,100 | 2,300 | 2,460 | 2,620 | 2,830 | 3,060 | ||
| Height(H) | 1,690 | 1,780 | 1,780 | 1,920 | 2,150 | 2,270 | ||
Fuel consumption in the above specification table is based on the following..
- Low-level calorific value
① Boiler kerosene : 44,116kJ/kg{10,300kcal/kg}
② Heavy oil : 40,813kJ/kg{9,750kcal/kg}
③ LNG : 41.9KJ/N㎥{10,000kcal/N㎥}
④ Propane : 93.8KJ/N㎥{22,400kcal/N㎥}
⑤ LPG+AIR : 57.8KJ/N㎥{13,800kcal/N㎥}
Consultation and quotes
Tell us where the boiler will be installed and what it is for.
Our engineers will get back to you.